Add to Cart
Range | -0.1MPa...0kPa~10kPa...100MPa |
Overload capability | Below 10MPa ≤ 2 times full scale 10MPa and above ≤1.5 times full scale |
Pressure Type | G (gauge pressure), A (absolute pressure), S (sealed gauge pressure) |
Accuracy | 0.1% (custom), 0.25% (typical), 0.5% (maximum) |
Long-term stability | ±0.1%FS/year (typical), ±0.2%FS/year (maximum) |
Zero temperature drift | ±0.03%FS/°C (≤100kPa), ±0.02%FS/°C (>100kPa) |
Sensitivity temperature drift | ±0.03%FS/°C (≤100kPa), ±0.02%FS/°C (>100kPa) |
Compensation temperature | 0°C~50°C(≤100kPa), -10°C~70°C(typical) |
Working temperature | -40°C~80°C, -20 ° C ~ 60 ° C (explosion-proof type) |
Power supply | 15~ 30V (Default 24V) |
Live display | 4-digit LED or LCD |
Output Signal | 4mA~20mA (superimposable HART protocol) RS485 (can output 4mA~20mA signal at the same time) |
Load Resistance | Current type: ≤ (U-12) / 0.02 (Ω) |
Explosion-proof grade | Intrinsically safe type: Ex d IIC T5 Gb |
Protection level | IP65/IP67 |